Chapter 6: Operation
Chapter 6: Operation
After installation and programming have been completed,
CPP Monitor 2000 is fully operational. This chapter explains how
CPP Monitor 2000 operates.
PART ONE: ALARM DIALOUT AND ACKNOWLEDGMENT
There are 3 stages to a complete alarm event: 1) Alarm Recognition,
2) Alarm Notification, 3) Acknowledgment. Note that not all alert
conditions will go through each stage. For example, some may not
meet the recognition time.
Alarm Recognition:
1) CPP Monitor 2000 monitors 8 inputs plus power failure. When the
status of an input changes or exceeds user-programmed limits, it
causes an alert condition.
2) If the alert condition lasts long enough to meet its programmed
recognition time, the alert condition becomes an alarm and
CPP Monitor 2000 begins the alarm notification sequence.
Alarm Notification:
CPP Monitor 2000 can make 6 types of phone calls: Voice, Fax, E-
mail, Modem, Beeper, and Alphanumeric pager.
Dialout Note: Call Progress
CPP Monitor 2000 monitors call progress when dialing out. If
CPP Monitor 2000 dials out and encounters a busy signal or no
answer within 30 seconds, the unit hangs up, waits the programmed
intercall delay time, and then dials the next phone number.